Glow Brand · Boiler troubleshooting

Boiler pressure keeps dropping / FILL shows

Glow B85/B120/B160

What is going on

Before touching anything, understand what the display is telling you. The B85, B120 and B160 boiler loses system pressure and the display asks for a fill. A boiler cannot fire safely without enough water, so the control blocks the burner when pressure drops too far. Find where the water is going before simply topping it up again, because a repeating pressure drop means a leak or an expansion problem. Hot water and pressure can scald, so let the system cool first.

Likely causes

  • System leak somewhere in the piping, radiators, fittings or underground lines
  • Expansion tank precharge wrong, or the tank diaphragm has failed
  • Relief valve weeping or discharging
  • No automatic fill valve, so pressure slowly drifts down
  • Pressure sensor reading wrong while the external gauge is fine

Check in this order

  1. Fill to about 16 psi when the system is cold, and note the starting number. The burner is blocked below 4 psi (Err 116) and immediately below 10 psi (Err 162).
  2. Watch the gauge over the next day or two with the system cold and again when hot, to see when it drops.
  3. Check the expansion tank precharge matches system pressure, with the tank isolated and drained as required. A waterlogged tank makes the relief valve discharge and pressure fall.
  4. Look at the relief valve and its discharge pipe for drips or mineral crust, since a weeping valve is easy to miss.
  5. Look for leaks at every joint, valve and radiator, including underground piping. Damp ground or a running meter are clues.
  6. Consider an automatic fill valve where local codes allow it.
  7. If pressure on the external gauge is fine but the display still says FILL, clean or replace the pressure sensor.
  8. Call a licensed tech if you cannot find the loss.

Applies to: B85, B120, B160 (NG and LP)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 10.1 p.47, 12.2 p.64-65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.