Boiler shows FILL and will not fire
What is going on
Display shows FILL, burner will not fire. Low water pressure is the lock.
Likely causes
- Water pressure below 4 PSI at the boiler inlet
- Water pressure below 10 PSI, which the pressure sensor uses to inhibit firing
- Slow leak, failed expansion tank or fill valve that is not holding pressure
Check in this order
- Read the pressure on the boiler gauge or display, with the system cold.
- Refill the system to at least 10 PSI.
- Find and repair leaks, because pressure that keeps dropping means water is going somewhere.
- Check the expansion tank charge and the fill valve.
- Confirm the burner fires after pressure is restored.
Applies to: C95 & C140
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand C95 & C140 installation & operation manual, pp. 33-34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.