Raising return temperature with a shunt pump (circuit diagram 3)
What is going on
Shunt pump control to keep the boiler return temperature above the required minimum.
Likely causes
- Return temperature falls below the required minimum value
Check in this order
- Check that sensor T2 is connected and switches the shunt pump on when the return is low.
- If the minimum return temperature is still not reached, reduce the boiler supply by at least 50% using sensor T1.
- Size the shunt pump so that bypassed water is about 30% of the boiler's total supply rate.
Applies to: Single-boiler system with shunt pump and mixing valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.