Weil-McLain · Boiler troubleshooting
Relief valve keeps letting out water
What is going on
The relief valve opens often. The relief valve is set at 30 psig. Usually the expansion tank is too small or has lost its air cushion.
Likely causes
- Expansion tank too small
- Expansion tank water-logged (no air cushion)
Check in this order
- Check the boiler pressure on the gauge. Normal cold fill on a house system is about 12 psig.
- Check the expansion tank. On a closed or diaphragm tank, check the air charge with an air pressure gauge.
- If the tank is water-logged, drain it and put the air cushion back.
- If the tank is too small for the system, replace it with a bigger one.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting p.7; System components (expansion tank) p.33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.