Viessmann · Boiler troubleshooting
Chimney height and termination
What is going on
Chimney flue must extend above the roof contact point and nearby roof structures as set out below. Only up to 8 in (200 mm) of flue above the cap counts toward height.
Check in this order
- Extend the flue at least 3 ft (1 m) above the highest point where the chimney touches the roof.
- Extend the flue at least 2 ft (0.6 m) above the roof surface or structure within 10 ft (3 m) horizontally.
- Do not count more than 8 in (200 mm) of flue above the chimney cap in the height calculation.
Applies to: Vitorond 100 VR1 oil-fired boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.