Heating and cooling piping arrangement
What is going on
Boiler piping when the same system also provides chilled water.
Check in this order
- Pipe the chiller in parallel to the boiler with valves so chilled water cannot enter the boiler.
- Fit flow control valves or other automatic means where coils in air handlers may see refrigerated air, to stop gravity circulation of boiler water during cooling.
- Set valve V1 open and V2 closed for the heating season; reverse them for the cooling season.
- Tag the valves with their purpose.
- Run the circulating pump from its own on/off switch, not the boiler pump aquastat.
Applies to: Vitorond 200 VD2A boilers in heating/cooling systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A installation manual, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.