Viessmann · Boiler troubleshooting

Boiler venting route

Vitodens 200-W B2HB

What is going on

The boiler comes with a pre-installed vent adaptor. The venting may be single-wall or coaxial and must be routed through a side wall or roof.

Check in this order

  1. Run the venting system (single-wall or coaxial) through a side wall or the roof.
  2. Use the shortest possible route.
  3. Keep a rising slope of at least 3 degrees toward the terminal.
  4. If a single-wall venting system is used in a boiler-room-air-dependent installation, remove the outer gasket.
  5. Support all piping by a proper suspension method. Piping must not rest on or be supported by the boiler.
  6. Use a moderate amount of pipe dope.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.