Weil-McLain · Boiler troubleshooting

Operate and test the boiler relief valve

Evergreen Series 2

What is going on

Test the relief valve so it opens and reseats properly. A metal discharge line must already be piped to a safe drain location, installed by a qualified installer.

Likely causes

  • Valve seat debris causing weeping
  • Blocked valve or discharge line

Check in this order

  1. Confirm the relief valve outlet is piped to a safe discharge location.
  2. Read the pressure/temperature gauge and record the system pressure.
  3. Lift the relief valve top lever slightly and let water flow through the valve.
  4. Release the lever and let the valve seat. Watch the discharge pipe to confirm it does not weep after it drains.
  5. If the valve weeps, lift the lever again to clean the seat. If it still weeps, have a qualified technician inspect the valve and system.
  6. If no water flows when the lever is fully lifted, shut down the boiler and call a qualified service technician.
  7. Confirm the gauge pressure returns to the recorded pressure. If not, call a qualified service technician.

Applies to: Evergreen Series 2 110/155/220/299/300/399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Condensing Gas Boiler User's Information Manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.