Viessmann · Boiler troubleshooting
Seal test for flue gas leaks during operation
What is going on
Leak check of burner door and flue gas components while the boiler runs. Viessmann says to check with the boiler at operating temperature.
Likely causes
- Gasket leaks on burner door or flue gas components
- Leaks at flue gas collector or insulation
Check in this order
- Check gaskets on the burner door and flue-gas-carrying components with an inspection mirror while the boiler is running.
- If needed, remove the thermal insulation parts to see the components.
- Look for condensate on the outside of the flue gas collector or insulation, which indicates a leak.
- Check the burner settings with the boiler heated to operating temperature (min. 40°C/104°F).
- Also check the burner at partial load.
Applies to: Vitocrossal 200 CI2 gas condensing boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Service Instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.