Venting safety requirements and draft checks

Vitorond 100

What is going on

The vent must carry all combustion products safely outdoors and must never pass through return, supply, ventilating or combustion air ducts. The boiler must never run without a vent. Check the building for exhaust devices that could depressurize it, and tell the owner in writing if they could affect the appliance.

Likely causes

  • Blocked vent, chimney or termination from birds' nests, ice, snow or debris
  • Unlined chimney or improper size
  • Downdraft or condensation in the flue
  • Positive-pressure mechanical draft connected to the vent

Check in this order

  1. Confirm the vent is not blocked and terminates outdoors.
  2. Check the chimney is lined, sized and in good condition.
  3. Confirm the chimney gives enough draft in the mildest weather the boiler will run in.
  4. Connect the boiler only to a chimney used for no other appliance, unless code allows it.
  5. Correct any downdraft or condensation problem before finishing.
  6. Check oil appliances have sufficient draft at all times.

Applies to: Vitorond 100 VR1 oil-fired boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 100 VR1 installation and service instructions, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.