Combustion air duct requirements
What is going on
Outdoor air ducts must meet these size rules. Sizing for openings is in the combustion air opening table.
Check in this order
- Make the duct cross-sectional area along its full length at least equal to the free area of the openings it connects.
- Keep the minimum duct dimension at 3 in (76 mm) at any section.
- Keep the outside air intake at least 1 ft (0.3 m) above the expected snow level.
- If a damper is in a combustion air opening, interlock it so no burner can start until the damper is fully open.
Applies to: VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.