Weil-McLain · Boiler troubleshooting
Vent and air piping - joints, elbows, slope and supports
What is going on
General rules for routing vent and air piping from the boiler to the termination.
Check in this order
- Use a locking collar on every polypropylene vent joint. Missing collars can cause leaks.
- Use sweep elbows only. Do not use short-radius elbows.
- Add a vent adapter or reducer if needed, following the vent manufacturer's instructions.
- Slope horizontal vent piping back toward the boiler at least 1/4 in per foot, or steeper if the vent maker requires it.
- Keep total vent length within the maximum in Figure 22 (p. 36). Reduce the maximum for each elbow as the figure shows.
- Install the termination before running piping from the boiler to it.
Applies to: SVF 500/600 Category IV direct vent and direct exhaust piping
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 Series 1 boiler manual, p. 57-58. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.