Configuring a multi-boiler cascade system
What is going on
Coding order for a multi-boiler system with a Vitotronic 300-K and boiler control units.
Check in this order
- Set code 2 01:2 on each Vitotronic 200 for a multi-boiler system with Vitotronic 300-K.
- Set a unique boiler number on each boiler (07:1 for boiler 1, 07:2 for boiler 2, and so on).
- On the Vitotronic 300-K, set general code 7E:0 for systems without a positive pressure flue gas cascade.
- On the Vitotronic 300-K, set cascade code 35 to match the number of boilers (35:2 for two, 35:3 for three, 35:4 for four, up to 8).
- If a Vitotronic 200-H is installed, set general code 97:1 so the outside temperature is accepted by the LON bus.
Applies to: Multi-boiler cascade with Vitotronic 300-K
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 and 300-K installation and service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.