Massachusetts sidewall horizontal vent carbon monoxide and signage requirements

SlimFit Series 2

What is going on

For sidewall horizontally vented gas equipment in residential buildings where the vent termination is less than 7 feet above finished grade, Massachusetts rules add detector and signage requirements.

Likely causes

  • Sidewall vent termination less than 7 feet above grade in residential use

Check in this order

  1. Confirm a hard-wired CO detector with alarm and battery backup is on the floor where the gas equipment is installed.
  2. Confirm a battery-operated or hard-wired CO detector with alarm is on each additional level served.
  3. If the equipment is in a crawl space or attic, the hard-wired detector may go on the next adjacent floor level.
  4. If requirements cannot be met at completion, the owner has 30 days to comply, and a battery-operated CO detector with alarm must be installed during that time.
  5. Use detectors that comply with NFPA 720 and are ANSI/UL 2034 listed and IAS certified.
  6. Install a metal or plastic sign on the exterior at least 8 feet above grade, directly in line with the vent terminal, with text at least 1/2 inch high reading: GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
  7. Leave the installation instructions and venting parts list with the appliance at completion.

Applies to: SlimFit 1000-2000 Series 2 sidewall horizontal venting in Massachusetts

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.