Viessmann · Boiler troubleshooting
Sidewall vent location and wind
What is going on
Locate the sidewall vent termination on the wall least affected by prevailing wind, since high wind can cause flue recirculation, poor combustion, and inlet condensation. Shield with a fence or shrubs if needed. A protective screen is required on sidewall vent installations.
Likely causes
- High wind causing flue recirculation
- Recirculation causing poor combustion and inlet condensation
Check in this order
- Select the wall least exposed to prevailing winds.
- Shield the termination with a fence or planting if wind is a problem.
- Install a protective screen on the sidewall termination.
- Keep total equivalent vent length within the limit.
Applies to: Sidewall vent terminations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Installation Instructions, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.