Navien · Boiler troubleshooting
Mounting the wall bracket and boiler
What is going on
Wall mount the boiler using the bracket from the L box. Use the fastener that suits the wall type. Do not mount on drywall without reinforcement.
Check in this order
- Remove the wall bracket from the L box.
- Mount the anti-vibration rubber pad with its arrow pointing up.
- Wood stud wall fasten the bracket with the lag bolts provided.
- Concrete wall drill a 3/8 in diameter hole 3-1/2 in deep, insert the anchor and fasten with the anchor bolts provided.
- Metal stud wall fasten with field-supplied toggle bolts rated for 100 lb each.
- Unfasten the 4 front cover latches (2 top, 2 bottom) to remove the cover before mounting the boiler.
Applies to: NFB-301C/399C
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NFB-C quick installation guide, p. 1. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.