Weil-McLain · Boiler troubleshooting

Boiler relief valve testing and replacement

EGPEG

What is going on

Keep the relief valve working. Replace it if it weeps or will not seat. Do not set the boiler limit control above 10 PSIG.

Likely causes

  • Valve weeping or not seating
  • Corrosion or deposits in the valve body
  • Limit control set above 10 PSIG

Check in this order

  1. Before testing, confirm the discharge pipe is connected to the valve outlet and arranged to safely dispose of discharge. Wear gloves.
  2. Test the relief valve at least monthly during the heating season to confirm the valve and discharge piping flow freely. Test more often if corrosion or deposits are seen.
  3. With the system at operating pressure, lift and hold the test lever fully open for at least 5 seconds, then release it and let the valve snap shut (try lever test).
  4. Perform the try lever test at the end of any non-service period.
  5. If the valve weeps or will not seat properly, replace it.
  6. Have a licensed plumbing contractor or authorized inspection agency reinspect the relief valve at least once every three years. This is not an owner task.
  7. Check the boiler limit control setting. It should never be set above 10 PSIG.

Applies to: EG and PEG Series 7 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.