Wire a boiler return mixing valve or modulating valve actuator (VD2/VD2A/CT3)
What is going on
Connect a 120 V or 24 V valve actuator through a valve adaptor on the control's DIN rail.
Check in this order
- Disconnect power to the control.
- Mount the 120 V or 24 V valve adaptor on the DIN rail in the connection enclosure.
- Plug the gS plug into socket gS on the control.
- Secure the cable with a tie (see page 21).
- Connect the adaptor's black wire to terminal aBH on the DIN rail, terminal 8, 9 or 10.
- Connect the valve actuator wires to the adaptor terminals as shown in the wiring diagrams.
Applies to: VD2, VD2A, CT3 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 GW2 installation and service instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.