Weil-McLain · Boiler troubleshooting

Zoning with circulators: three space heating zones plus indirect DHW piped to boiler

SVF 500/600 Series 1

What is going on

Three space heating zones and one indirect DHW aquastat on the boiler control.

Check in this order

  1. Review the wiring in Sections B and C (pages 72 and 73).
  2. Wire the DHW aquastat to Input 1 (J17-1/2).
  3. Wire space heating thermostats to Inputs 2, 3 and 4.
  4. Assign Inputs 2, 3 and 4 to PRIORITY 2 and choose the matching heating system type in the Wizard or in the PRIORITY 2 menu.
  5. Assign Input 1 to PRIORITY 1 so DHW takes precedence.
  6. Use the factory default DHW and heating system settings, or change them if needed.

Applies to: SVF 500/600 boilers with indirect DHW tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 boiler manual, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.