Viessmann · Boiler troubleshooting
Boiler in heating/cooling application
What is going on
When the boiler is used with a refrigeration system, the chilled medium must be piped in parallel with the boiler using valves that keep chilled medium out of the boiler. Air handler heating coils exposed to refrigerated air need flow control valves or other automatic means to stop gravity circulation during cooling. Check the chiller manufacturer's requirements. The circulating pump must run from a separate on/off switch, not the boiler pump aquastat.
Check in this order
- Label the changeover valves v1 and v2.
- Cooling season close valve v1 and open valve v2.
- Heating season close valve v2 and open valve v1.
- Run the circulating pump from a separate on/off switch, not the boiler aquastat.
Applies to: Boiler connected to a chiller or cooling coils
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A Installation Instructions, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.