Viessmann · Boiler troubleshooting

Checking the condensate drain and cleaning the siphon trap

Vitodens 100-W B1HE/B1KE

What is going on

A dry or unfilled siphon trap lets flue gas escape. Route the drain hose with no bends and a constant fall.

Likely causes

  • Debris in the siphon trap
  • Trap not filled or not seated

Check in this order

  1. Cover electronic components with watertight material.
  2. Move the bracket with the programming unit to the maintenance position.
  3. Remove the supply hose.
  4. Pull the siphon trap up out of the drain hose, keeping it level so condensate does not spill.
  5. Clean the siphon trap.
  6. Fill the siphon trap with water and refit it on the drain hose.
  7. Refit the supply hose and make sure the clip is sealed and closed.
  8. Check connections for leaks and confirm the trap is seated correctly.
  9. Remove any condensate that escaped before commissioning. Do not start the boiler until the trap is filled.

Applies to: Condensate drain and siphon trap

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.