Viessmann · Boiler troubleshooting
Checking the condensate drain and cleaning the siphon trap
What is going on
A dry or unfilled siphon trap lets flue gas escape. Route the drain hose with no bends and a constant fall.
Likely causes
- Debris in the siphon trap
- Trap not filled or not seated
Check in this order
- Cover electronic components with watertight material.
- Move the bracket with the programming unit to the maintenance position.
- Remove the supply hose.
- Pull the siphon trap up out of the drain hose, keeping it level so condensate does not spill.
- Clean the siphon trap.
- Fill the siphon trap with water and refit it on the drain hose.
- Refit the supply hose and make sure the clip is sealed and closed.
- Check connections for leaks and confirm the trap is seated correctly.
- Remove any condensate that escaped before commissioning. Do not start the boiler until the trap is filled.
Applies to: Condensate drain and siphon trap
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.