Example E - purpose and piping with DHW storage tank

Evergreen Series 2

What is going on

Variable-primary piping with a DHW storage tank directly piped to one boiler (Boiler 2). DHW is given priority on Boiler 2, which stops network heating on that boiler, while Boiler 1 keeps serving the network. This arrangement has no DHW redundancy and DHW is only available when Boiler 2 is running. A differential pressure by-pass valve is recommended in case a motorized valve fails, to prevent dead-heading the system pump. A 2-way motorized valve with an end switch is recommended and the end switch should wire into the proof-of-closure circuit.

Check in this order

  1. Size the DHW tank and DHW pump for the required load and a flow through the boiler and tank within the allowable range in the sizing table.
  2. Pipe the DHW circulator to the Shadow 2 boiler.
  3. Install a differential pressure by-pass valve (Item 38) in the system piping.
  4. Install 2-way motorized isolation valves (Item 17a) with end switches wired to the proof-of-closure circuit.
  5. Install the system and return immersion sensors within 6 pipe diameters, and no more than 3 feet, from the first and last boiler tees.

Applies to: Example E variable primary piping with direct DHW tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Evergreen Series 2 advanced manual, p. 35-36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.