Install the outdoor temperature sensor for outdoor reset
What is going on
Mounts the outdoor sensor so the boiler can adjust supply temperature to outdoor conditions. Keep the sensor away from direct sun and artificial heat.
Check in this order
- Mount the sensor on a north-facing wall under an eave, out of direct sunlight.
- Keep the sensor away from vents, ducts or other heat sources.
- Run minimum 18 AWG wire back to the outdoor sensor terminal on the boiler.
- Remove the front panel (two screws) and connect the sensor to the terminals in the PC board enclosure.
- Make sure Parameter 00 is set to A (default).
- Set Parameters 01 to 03 for the application.
Applies to: I-Series Plus Condensing Combi Boiler with outdoor reset
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 93-94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.