Check room temperature sensor

Vitotronic 200-H

What is going on

Test the separate room temperature sensor used when the remote control cannot be mounted in a suitable place.

Likely causes

  • Displayed room temperature differs significantly from actual room temperature

Check in this order

  1. Disconnect the wires at the sensor terminals.
  2. Measure resistance at terminals 9 and 13b.
  3. Compare with the resistance table.
  4. Compare with the displayed room temperature (see page 25).
  5. If the difference is significant, check installation and replace the sensor if needed.

Applies to: Room temperature sensor Part No. 7133 379

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H HK1M installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.