Viessmann · Boiler troubleshooting
Check room temperature sensor
What is going on
Test the separate room temperature sensor used when the remote control cannot be mounted in a suitable place.
Likely causes
- Displayed room temperature differs significantly from actual room temperature
Check in this order
- Disconnect the wires at the sensor terminals.
- Measure resistance at terminals 9 and 13b.
- Compare with the resistance table.
- Compare with the displayed room temperature (see page 25).
- If the difference is significant, check installation and replace the sensor if needed.
Applies to: Room temperature sensor Part No. 7133 379
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H HK1M installation and service instructions, p. 39. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.