Viessmann · Boiler troubleshooting

Checking mixing valve movement and leak tightness

Vitocrossal 300 CA3B Dual Fuel

What is going on

Mixing valve is checked with the motor lever disengaged.

Check in this order

  1. Remove the motor lever from the mixing valve handle.
  2. Check the mixing valve moves freely.
  3. Check the mixing valve for leaks. Replace the O-ring if it leaks.
  4. Re-engage the motor lever.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.