Navien · Boiler troubleshooting
Power gateway from the boiler PCB
What is going on
The gateway can take power from the boiler controller's gateway power terminal instead of the supplied power supply.
Check in this order
- Connect the gateway power terminal pin 2 (AC24VL, V+) and pin 1 (AC24VN, V-) to the boiler PCB 3-pin connector.
- Connect frame ground (FG) to the boiler frame ground.
- Confirm the input is 12-24 VDC or 24 VAC, per the manual.
Applies to: Gateway power from boiler PCB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.