Low water cut-off (LWCO) test
What is going on
The LWCO is built into the Boiler Out sensor at the highest point of the heat exchanger. Two test methods are given.
Check in this order
- Method 1 press and hold the gray LWCO test button below the J8 and J9 connectors for at least 5 seconds.
- Method 2 turn off the boiler and the circulating pump (if used), isolate the boiler and drain the water level below the LWCO sensor.
- For method 2, turn the boiler on. It should not run and should show a Low Water fault.
- Expected result for either method a manual lockout reset with LOW WATER on the display.
- If water was drained, turn the boiler off, refill the system, restart the pump if used, turn the boiler on, then reset from the display Reset button.
Applies to: SVF 500/600 boilers, LWCO sensor on connector J9
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.