Viessmann · Boiler troubleshooting

Connect flue outlet to venting

Vitocrossal 200 CI2

What is going on

Connect the flue collar to the venting so that no load or torque is on the boiler collar. Install a flue gas adaptor if the stainless vent does not fit the collector directly. The collector is not built to carry the weight of the vent.

Check in this order

  1. Fully insert the flue gas adaptor into the flue outlet if one is used with stainless pipe.
  2. Fully seat the vent into the flue gas collector.
  3. Use the shortest run to the flue pipe with a slight rise of at least 2-3 degrees and avoid sharp bends.
  4. Support all venting components on an anchoring system per the vent maker.
  5. Check all joints for leaks with a certified leak detector.

Applies to: Vitocrossal 200 CI2 flue connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.