Navien · Boiler troubleshooting
Check and adjust gas/air ratio at low fire
What is going on
Verify CO2 or offset at low fire and adjust the gas valve set screw if needed.
Check in this order
- Open several DHW fixtures on full hot and set the boiler to 1-stage MIN mode.
- Remove the plate and gasket to reach the emissions port, then insert the combustion analyzer.
- Measure CO2 at low fire and compare it to Table 2.
- If CO2 is outside 0.5% of the table value, remove the screw-on cover over the set screw.
- Using a 5/32 in or 4 mm Allen wrench, turn the set screw no more than 1/4 turn clockwise to raise or counterclockwise to lower CO2.
- Turn on the gas and water supply, then leak test all gas connections before operation.
- If using a digital manometer, loosen the offset port screw two turns and connect the positive side to the offset pressure port.
- Compare the low fire offset with Table 3 and adjust the set screw the same way if it is out of range.
- Set 2-stage D. MAX and check CO2 at high fire. If it does not match Table 2, do not adjust the gas valve; check the gas orifice.
Applies to: NCB700 gas/air ratio
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 143. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.