Navien · Boiler troubleshooting
External recirculation with NaviCirc
What is going on
DHW recirculation loop using a NaviCirc valve on the faucet furthest from the boiler and a recirculation pump.
Check in this order
- Select the Intelligent or Weekly option in the external recirculation DHW menu for best performance.
- To use aquastat control, install an aquastat on the DHW line and connect it to terminal CNC6 on the PCB.
- Install the NaviCirc recirculation valve on the faucet furthest from the boiler.
- Use a recommended recirculation pump (see the pump setting table on this page).
- Keep the recirculation pipe within the maximum length table.
Applies to: NCB700 DHW recirculation
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.