Viessmann · Boiler troubleshooting
Application 4: ZC1 setpoint demand with ZC2 weather compensated
What is going on
ZC1 is a low-temperature on/off circuit with an outdoor reset curve during a thermostat call. ZC2 (air handler) runs a fixed setpoint. A thermostatic mixing valve is needed to protect ZC1 when the air handler is running. ZC1 uses pump output 28/20. The ZC2 call starts the 157 plug pump.
Check in this order
- Select the number of zone circuit connections to match the thermostats on the DE connections, then press OK.
- Select Weather Compensated for ZC1 and press OK.
- Confirm the ZC1 settings and press OK. These can be changed later.
- Assign the ZC1 pump as the 28/20 output.
- Set ZC2 to Fixed Setpoint and press OK.
- Enter the ZC2 zone target temperature.
- For ZC2 pump, select the 157 Output. If the air handler controls the pump, select No Output.
- Review the output summary and finish start-up.
Applies to: Application 4 (CU3I 2ZC2ZP.01)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A Application Guide, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.