What is going on

ZC1 is a low-temperature on/off circuit with an outdoor reset curve during a thermostat call. ZC2 (air handler) runs a fixed setpoint. A thermostatic mixing valve is needed to protect ZC1 when the air handler is running. ZC1 uses pump output 28/20. The ZC2 call starts the 157 plug pump.

Check in this order

  1. Select the number of zone circuit connections to match the thermostats on the DE connections, then press OK.
  2. Select Weather Compensated for ZC1 and press OK.
  3. Confirm the ZC1 settings and press OK. These can be changed later.
  4. Assign the ZC1 pump as the 28/20 output.
  5. Set ZC2 to Fixed Setpoint and press OK.
  6. Enter the ZC2 zone target temperature.
  7. For ZC2 pump, select the 157 Output. If the air handler controls the pump, select No Output.
  8. Review the output summary and finish start-up.

Applies to: Application 4 (CU3I 2ZC2ZP.01)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A Application Guide, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.