Viessmann · Boiler troubleshooting
Connect several remote controls
What is going on
Use an on-site terminal box when more than one remote control is connected. The total KM BUS cable length should be limited, and each remote branch should be kept short.
Check in this order
- Install a terminal box on site.
- Connect the control unit to the terminal box.
- Connect each remote control (Vitotrol 1, 2, 3) to the terminal box as shown in the diagram.
- Keep each remote branch to 15 m (50 ft) maximum.
- Keep the total KM BUS cable length to 50 m (164 ft) maximum.
- If additional KM BUS participants are present, connect them through the same terminal box as shown in the version 2 diagram.
Applies to: Vitotrol remotes on KM BUS
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 134-135. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.