Checking the boiler, DHW tank, supply or low-loss header temperature sensors
What is going on
Warning: the boiler temperature sensor is in the heating water (scalding risk), so drain the boiler before replacing it. Sensor type is NTC 10 kΩ. Only one supply or low-loss header temperature sensor may be used.
Check in this order
- Boiler sensor remove the lead to boiler water temperature sensor A and check the resistance.
- DHW tank sensor pull plug from the cable harness at the control unit and check the resistance.
- Supply or low-loss header sensor pull plug X3 from the control unit and check the resistance across terminals X3.4 and X3.5.
- Compare the actual values with the curve.
- Replace the sensor if the deviation is severe.
Applies to: Vitodens 222-F B2TB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.