Viessmann · Boiler troubleshooting

Checking the boiler, DHW tank, supply or low-loss header temperature sensors

Vitodens 222-F

What is going on

Warning: the boiler temperature sensor is in the heating water (scalding risk), so drain the boiler before replacing it. Sensor type is NTC 10 kΩ. Only one supply or low-loss header temperature sensor may be used.

Check in this order

  1. Boiler sensor remove the lead to boiler water temperature sensor A and check the resistance.
  2. DHW tank sensor pull plug from the cable harness at the control unit and check the resistance.
  3. Supply or low-loss header sensor pull plug X3 from the control unit and check the resistance across terminals X3.4 and X3.5.
  4. Compare the actual values with the curve.
  5. Replace the sensor if the deviation is severe.

Applies to: Vitodens 222-F B2TB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.