Viessmann · Boiler troubleshooting
Gas supply pressure out of range
What is going on
Running pressure at high fire is outside the allowed band.
Likely causes
- Supply pressure too low (under 4 w.c. NG or under 10 w.c. LPG).
- Supply pressure too high (over 14 w.c.).
Check in this order
- Do not adjust the gas valve for pressure problems.
- If pressure is low, call the local gas utility to increase supply pressure.
- If pressure is high, call the local gas utility to decrease supply pressure.
- Do not operate the boiler at pressures over 14 w.c. at the valve.
Applies to: Vitodens 100-W WB1B gas supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.