Viessmann · Boiler troubleshooting

Gas supply pressure out of range

Vitodens 100-W WB1B

What is going on

Running pressure at high fire is outside the allowed band.

Likely causes

  • Supply pressure too low (under 4 w.c. NG or under 10 w.c. LPG).
  • Supply pressure too high (over 14 w.c.).

Check in this order

  1. Do not adjust the gas valve for pressure problems.
  2. If pressure is low, call the local gas utility to increase supply pressure.
  3. If pressure is high, call the local gas utility to decrease supply pressure.
  4. Do not operate the boiler at pressures over 14 w.c. at the valve.

Applies to: Vitodens 100-W WB1B gas supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.