Navien · Boiler troubleshooting
High altitude derate and conversion
What is going on
Above 2,000 ft the boiler derates. Natural gas needs an orifice change above 5,400 ft. Propane needs the propane conversion kit at any elevation the unit is used at.
Check in this order
- Set DIP SW 2 for the install elevation.
- Above 2,000 ft, expect a 3% derate per 1,000 ft on natural gas.
- Above 2,000 ft, expect a 4% or more derate per 1,000 ft on propane.
- For natural gas above 5,400 ft, change the gas orifice to the high altitude orifice. Do not confuse it with the LP orifice.
- For propane at any altitude up to 10,100 ft, use the Propane Gas and High Altitude Conversion Kit.
- The natural gas high altitude kit is inside the cabinet. Remove the front cover to reach it.
- Check the orifice against the Natural Gas High Altitude Conversion Guide and replace it if required.
- Common vent installs are only approved up to 4,500 ft.
Applies to: Gas type and elevation changes
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 78-79. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.