Connect PVC/ABS vent or air pipe to the boiler adapter

Ultra Series 4

What is going on

Use a smooth, chamfered pipe end so the adapter gasket seals. The clamp only holds the pipe; the seal comes from the internal gasket.

Check in this order

  1. Cut the pipe square, then clean and chamfer the insertion end. Deburr the inside of the insertion end and clean and deburr both ends.
  2. Check the adapter for obstructions or foreign objects.
  3. Loosen the adapter clamp screw.
  4. Measure 3-1/2 inches from the pipe end and mark it.
  5. Apply a small amount of silicone grease to the pipe end.
  6. Insert the pipe into the adapter and slide it down until the 3-1/2 inch mark reaches the adapter.
  7. Tighten the adapter clamp securely but do not overtighten.
  8. Do not force the pipe or bend the adapter when inserting.

Applies to: Ultra boiler vent and air connectors

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.