Replacing the PC board

Vitotronic 200-H

What is going on

Procedure for swapping the Vitocontrol-C PC board, including how to restore the model-specific coding.

Check in this order

  1. Record all codes and adjustments made at the control unit.
  2. Replace the PC board.
  3. Set code 8A:176 and coding address 92 to 92:172 for model HK1S, or 92:173 for model HK3S.

Applies to: HK1S and HK3S

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H Installation and Service Instructions, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.