Viessmann · Boiler troubleshooting
Enclosure installation sequence
What is going on
Build the jacket around the boiler in order. Components are supplied in the jacket carton and insulation mounting parts come with the insulation.
Check in this order
- Install the crossbar supports per the model table.
- Attach rear mounting brackets with M8 bolts, spaced 41 in. (1044 mm) outside, in line with the outer edges of the tie bars.
- Fasten front left and right mounting brackets to the upper hinge bolts with M12 nuts, longer extenders at top with edge pointing back. Keep 43 in. (1090 mm) outside span between front brackets.
- Insert B 3.9 x 9.5 sheet metal screws into the side edging, leaving 2 mm (0.07 in.) room.
- Fasten space brackets to the connecting panels with B 3.9 x 9.5 screws.
- Snap connecting panels and space brackets onto the lower anchor rod and tighten to the top span bracket(s).
- Lay insulation blankets on the outside of the boiler with the black side facing out.
- Secure the rear insulation blanket, cut-out facing rear, with tension spring to the outside blanket. Cover cuts with fiber rope seal.
- From the rear, push or pull the insulation mat under the full length of the cast iron block.
- Insert side panel hinges into mounting bracket slots per the side panel table. Slide the mid-panel (VD2-500 to VD2-1080) as needed.
- Insert the right and left rear panels with hinges into the side panels and fasten with B 3.9 x 9.5 screws.
- Mount the front panel and secure with B 3.9 x 9.5 screws.
- Mount the top panel on hooks into the side panels. Attach mid top panels (VD2-500 and up) with hooks.
- Secure rear top panel hooks and tighten to rear panels with B 3.5 x 9.5 screws.
- Fasten brackets to the rear panel with sheet metal screws.
- Mount the Vitorond 200 nameplate to the front panel.
Applies to: Vitorond 200 VD2 enclosure
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 installation manual, p. 28-30, 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.