Viessmann · Boiler troubleshooting

Check and adjust ignition and ionization electrodes

Vitocrossal 300 CU3A

What is going on

Electrode type depends on size: C is up to 35 kW (125 MBH), D is from 45 kW (160 MBH).

Likely causes

  • Worn or contaminated electrodes
  • Electrode gap out of specification

Check in this order

  1. Check electrodes for wear and contamination.
  2. Clean electrodes with a small brush (not wire) or sandpaper.
  3. Check electrode gaps against specification. Replace and align electrodes with new gaskets if gaps are wrong or electrodes are damaged.
  4. Tighten electrode fixing screws to 2.2 lb.ft (3.0 Nm).

Applies to: Vitocrossal 300 CU3A ignition and ionization electrodes

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.