Check direct vent (coaxial) system tightness
What is going on
Simplified leak test during start-up, measuring air in the coaxial gap of the air intake adaptor.
Likely causes
- Leak in the vent pipe or venting system
Check in this order
- Measure CO2 in the combustion air in the coaxial gap of the air intake adaptor, or at flapper A on the air inlet pipe just before the burner.
- Pass if CO2 is 0.2% or lower, or O2 is 20.6% or higher.
- If CO2 is higher or O2 is lower, check the venting system thoroughly.
Applies to: Direct vent coaxial venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.