Wire external limits for manual or automatic reset

SlimFit Series 2

What is going on

Factory jumper must be removed before a external limit is wired. Manual reset lockout needs a person at the boiler to reset. Cycling power does not reset a manual lockout.

Likely causes

  • Limit circuit opens during operation

Check in this order

  1. Remove the factory jumper on the chosen circuit.
  2. For manual reset, wire isolated limit contacts across P13 pins 1 and 2.
  3. For manual reset, the control locks out and the alarm contacts close when the limit opens.
  4. Reset manually using the procedure in this manual after the limit closes.
  5. For automatic reset, wire isolated limit contacts across P13 pins 3 and 4.
  6. For automatic reset, the burner shuts down when the limit opens and restarts 150 seconds after the limit closes.

Applies to: External limit inputs, terminal block P13

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.