Weil-McLain · Boiler troubleshooting
Wire external limits for manual or automatic reset
What is going on
Factory jumper must be removed before a external limit is wired. Manual reset lockout needs a person at the boiler to reset. Cycling power does not reset a manual lockout.
Likely causes
- Limit circuit opens during operation
Check in this order
- Remove the factory jumper on the chosen circuit.
- For manual reset, wire isolated limit contacts across P13 pins 1 and 2.
- For manual reset, the control locks out and the alarm contacts close when the limit opens.
- Reset manually using the procedure in this manual after the limit closes.
- For automatic reset, wire isolated limit contacts across P13 pins 3 and 4.
- For automatic reset, the burner shuts down when the limit opens and restarts 150 seconds after the limit closes.
Applies to: External limit inputs, terminal block P13
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.