Weil-McLain · Boiler troubleshooting

External high-limit and low water cutoff requirements

Ultra Series 4

What is going on

The U-Control provides high limit and low water protection by sensing the heat exchanger temperature. Some codes or jurisdictions require extra external controls. Use the external limit circuit on the P13 terminals when lower temperature circuits are on the system.

Check in this order

  1. If ASME or Canadian requirements apply, install a manual reset high temperature limit in the supply piping between the boiler and isolation valve, set not above 200 °F.
  2. The U-Control shuts the boiler down at 195 °F, or lower if set lower.
  3. For a manual reset external limit, connect series isolated contacts to P13 terminals 1 and 2. For an automatic reset limit, use P13 terminals 3 and 4.
  4. If the U-Control is manual reset with an external manual reset limit, set the U-Control boiler limit at least 20 °F below the external limit. Example: 180 °F for a 200 °F external limit.
  5. If a low water cutoff is needed, install an electrode probe-type cutoff designed for water in a tee in the supply piping above the boiler. Wire it per the field wiring section.

Applies to: All Ultra Series 4 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.