Viessmann · Boiler troubleshooting

Zone control wizard: single zone with fixed setpoint and 157 pump output

Vitocrossal 300 CU3A

What is going on

One zone circuit with a fixed setpoint. A low-temperature circuit uses a 3-way mixing valve, a high-temperature circuit ZC1, and an indirect DHW tank controlled by an aquastat on DE2. The DHW call turns on the 28/20 pump output. Heating curve settings control the HC2 mixing valve. Simultaneous space heating and DHW is possible, so size the boiler for it.

Check in this order

  1. Select the number of zone circuit connections to match the thermostats on the DE connections, then press OK.
  2. Confirm the Fixed Setpoint selection and press OK.
  3. Enter the target water temperature for a zone call.
  4. If the air handler has an internal pump, select No Output.
  5. If the air handler has no internal pump, select the 157 Output so the 157 plug pump runs on a ZC call.
  6. Check the output summary and finish start-up.

Applies to: Application with one zone circuit, fixed setpoint, 157 pump output

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A Application Guide, p. 36, 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.