Weil-McLain · Boiler troubleshooting
Check the thermostat circuit for stray voltage
What is going on
The thermostat terminals must never see voltage. Voltage there will damage the control.
Likely causes
- Wiring errors in the external circuit.
- Common with 3-wire zone valves.
Check in this order
- Disconnect the two external wires from the boiler thermostat terminals.
- Connect a voltmeter across the two incoming wires.
- Close each thermostat, zone valve and relay one at a time and read the voltage.
- If any voltage appears, find and correct the external wiring.
- Reconnect the wires and let the boiler cycle.
Applies to: Boiler thermostat terminals
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.