Check the thermostat circuit for stray voltage

SVF Series 1

What is going on

The thermostat terminals must never see voltage. Voltage there will damage the control.

Likely causes

  • Wiring errors in the external circuit.
  • Common with 3-wire zone valves.

Check in this order

  1. Disconnect the two external wires from the boiler thermostat terminals.
  2. Connect a voltmeter across the two incoming wires.
  3. Close each thermostat, zone valve and relay one at a time and read the voltage.
  4. If any voltage appears, find and correct the external wiring.
  5. Reconnect the wires and let the boiler cycle.

Applies to: Boiler thermostat terminals

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.