Viessmann · Boiler troubleshooting
Check mixing valve and gas line for leaks
What is going on
Check the gas mixing valve for smooth operation and leaks. Gas joints must be pressure tight at normal operating pressure.
Likely causes
- Worn O-rings on the mixing valve
Check in this order
- Disconnect the motorized lever from the mixing valve handle.
- Check that the mixing valve moves freely.
- Check the mixing valve for leaks. Replace the O-rings if it leaks.
- Snap the motorized lever back into place.
- Leak test the gas supply piping before putting the boiler into operation.
- Use approved leak detection liquid only and remove residue afterward.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.