Improper pilot burner flame
What is going on
A proper pilot is a blue flame, with the inner cone engulfing the pilot flame sensor and the sensor glowing cherry red. Compare the flame to these faults.
Likely causes
- Overfired: large flame lifting or blowing past the pilot flame sensor
- Underfired: small flame with the inner cone not engulfing the sensor
- Lack of primary air: yellow tip on the flame
Check in this order
- Check the flame against the proper pilot flame description.
- For an overfired or underfired pilot, adjust the gas supply to the pilot and recheck.
- For a yellow flame tip, check and correct primary air supply, then recheck.
- Confirm the pilot flame sensor glows cherry red once the flame is correct.
Applies to: Spark-ignited pilot CGi Series 5 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain CGi Series 5 boiler manual, p. 65. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.