Install the condensate trap
What is going on
Assemble the trap so the float is in place and the connections are sealed.
Check in this order
- Insert the 3/4 in PVC elbow through the trap inlet connection ferrule nut.
- Slide the trap inlet gasket up onto the 3/4 in PVC elbow.
- Confirm the trap float is in place.
- Tighten the inlet ferrule nut fully onto the trap.
- Slide the 1 in Fernco fitting onto the 3/4 in elbow and tighten the hose clamp with a 5/16 in nut driver or flat screwdriver.
- Confirm the bottom trap connection is fully tight.
- Slide the trap onto the heat exchanger condensate drain and tighten its hose clamp.
- Secure the trap bracket to the boiler base.
- Secure the trap to the bracket with the U-bolt.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.