Viessmann · Boiler troubleshooting
Connecting control unit power supply
What is going on
The control must be grounded. L, N and G must not be interchanged. The supply is 120VAC, 1 phase, 60 Hz, 12 A full load.
Check in this order
- Make sure the main supply has overcurrent protection rated at least 12 A and a 2-pole disconnect.
- Provide disconnect means and overcurrent protection as per local codes.
- Connect the supply wire to terminals 11, N and G on the DIN rail inside the junction box.
- Follow the National Electrical Code (NEC) and ANSI/NFPA 70 in the US, or the Canadian Electrical Code (CEC) and CSA C22.1 Part 1 in Canada, plus local codes.
Applies to: Vitotronic 200-H HK1B, power supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.