Condensate not draining, burner shuts down

What is going on

Condensing boilers make water as they burn, and it has to leave through the siphon and drain hose. If it can't, it backs up into the lower part of the boiler and the burner shuts down with fault message F.540 or A.18. On the Vitodens 200-W it is usually debris in the siphon, a sagging hose or a plugged neutralizer. It is a simple fix, but do it with power off.

Likely causes

  • Blocked siphon or drain hose, typically with scale or debris
  • Hose without constant fall, so a belly traps condensate
  • Neutralizer cartridge blocked with spent granules or sludge
  • Other appliance drains tied into the boiler condensate line
  • On common venting, flue gas collector siphon also plugged

Check in this order

  1. Turn power off at the boiler and cover the electronics, because you will be moving water around them. Move the control unit to service position.
  2. Pull off the supply hose and remove the siphon, with a bucket handy for the water inside.
  3. Clean the siphon thoroughly, refill it with water so it holds its seal, and refit it with the clip secure. A dry siphon lets flue gas out.
  4. Route the drain hose with constant fall and no bends or low spots. Keep an air gap before any neutralizer.
  5. Look at the neutralizer and clear or replace it if it is blocked or exhausted.
  6. Do not connect other appliance drains, for example softener backwash, to the boiler condensate line.
  7. On common venting, also clean the siphon in the flue gas collector.
  8. Restart and watch the drain run, then confirm the fault clears.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), p.31-32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.