Condensate not draining, burner shuts down
What is going on
If condensate cannot leave the boiler it collects in the lower part and the burner stops with a fault message (F.540 / A.18).
Likely causes
- Blocked siphon or drain hose
- Hose without constant fall
- Neutralizer blocked
Check in this order
- Cover electronics, move the control unit to service position, pull off the supply hose and remove the siphon.
- Clean the siphon, refill with water and refit with the clip secure.
- Route the drain hose with constant fall and no bends; keep an air gap before any neutralizer.
- Do not connect other appliance drains (e.g. softener backwash) to the boiler condensate line.
- On common venting, also clean the siphon in the flue gas collector.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), p.31-32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.