External 0-10 V boiler water temperature setpoint
What is going on
An external 0-10 V signal sets the maximum possible boiler water temperature. The voltage-to-temperature chart is not reproduced on this page, only one example.
Check in this order
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check that the polarity is correct.
- Use the chart to match the signal voltage to the maximum boiler water temperature.
- Example 8 VDC equals 176 ºF (80 ºC).
Applies to: Vitocrossal 300 CU3A 26 to 199, extension module EA1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Installation Instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.